Volume Flow Monitors

Display per page
Sort by
Product no.: 81530F3.1

Airflow monitor with linear analogue output

Power supply: 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm), 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature1: -25...+80°C 1

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range²: approx. 0.5-30m/s  (adjustable)

Sensor: integrated

Immersion depth: approx. 130mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP67

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1The Monitor is optionally also available with a stepped sensor with a cable length of 2,5m. Above 80°C the sensor needs to be stepped. Then the applicable range of media temperatures increases to -20°C up to 250°C / 350°C.

²Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s, optional 0.1-30m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

431.00 *
Delivery weight: 320 g
Product no.: 81530M8F3

Airflow monitor with linear analogue output

Power supply 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature: -25...+80°C 

(optionally up to +350°C)

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s (optionally up to 150m/s)

Sensor: integrated

Immersion depth: 50mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

 

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

² Other lengths possible (130/165/250/300mm).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

505.00 *
Product no.: Zubehör

Accessories for airflow sensors and RLSW-housing

Mounting flange, reducer, wall mounting set

WEEE-Reg.-Nr. DE 38909112

Product no.: 81530M8F8

Airflow monitor with linear analogue output

Power supply 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+250°C 

(optionally up to +350°C)

Temperature gradient: 30K/min 

Switch-point: adjustable via potentiometer

Measurement range1: 0.5-30m/s

(optionally up to 150m/s)

Sensor: integrated

Immersion depth: 50mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

580.00 *
Product no.: 81530M8F8/350°C

Airflow monitor with linear analogue output

Power supply: 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+350°C 

Temperature gradient: 30K/min 

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s

(optionally up to 150m/s)

Sensor: integrated

Immersion depth: 50mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

631.00 *
Product no.: 81535F3.1

Airflow monitor with linear analogue output (without LC-Display)

Power supply 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm), 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+80°C 1

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range²: approx. 0.5-30m/s  (set by manufacturer according to customer need, possible up to 120m/s)

Sensor: integrated

Immersion depth: approx. 130mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP67

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1The monitor is optionally also available with stepped sensor with a cable length of 2,5m. Above 80°C the sensor needs to be stepped. Then the media temperaure range raises to -20°C up to 250°C / 350°C.

²Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s, optionally 0.1-30m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

311.00 *
Delivery weight: 320 g
Product no.: 81535F3

Airflow monitor with linear analogue output (without LC-Display)

Power supply 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm), 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+80°C 1

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range²: approx. 0.5-30m/s  (set by manufacturer according to customer need, possible up to 120m/s)

Sensor: integrated

Immersion depth: approx. 50mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP67

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1The monitor is optionally also available with stepped sensor with a cable length of 2,5m. Above 80°C the sensor needs to be stepped. Then the media temperaure range raises to -20°C up to 250°C / 350°C.

²Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s, optionally 0.1-30m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

305.00 *
Delivery weight: 320 g
Product no.: 81535F3.2

Airflow monitor with linear analogue output (without LC-Display)

Power supply 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm), 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+80°C 1

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range²: approx. 0.5-30m/s  (set by manufacturer according to customer need, possible up to 120m/s)

Sensor: integrated

Immersion depth: approx. 165mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP67

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1The monitor is optionally also available with stepped sensor with a cable length of 2,5m. Above 80°C the sensor needs to be stepped. Then the media temperaure range raises to -20°C up to 250°C / 350°C.

²Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s, optionally 0.1-30m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

319.00 *
Delivery weight: 320 g
Product no.: 81535F3.3

Airflow monitor with linear analogue output (without LC-Display)

Power supply 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm), 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+80°C 1

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range²: approx. 0.5-30m/s  (set by manufacturer according to customer need, possible up to 120m/s)

Sensor: integrated

Immersion depth: approx. 300mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP67

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1The monitor is optionally also available with stepped sensor with a cable length of 2,5m. Above 80°C the sensor needs to be stepped. Then the media temperaure range raises to -20°C up to 250°C / 350°C.

²Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s, optionally 0.1-30m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

333.00 *
Delivery weight: 320 g
Product no.: 81535M8F3

Airflow monitor with linear analogue output

Power supply 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature: -25...+80°C 

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s (optionally up to 150m/s)

Separate sensor

Immersion depth: 50mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

384.00 *
Product no.: 81535M8F3.1

Airflow monitor with linear analogue output

Power supply 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature: -25...+80°C 

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s (optionally up to 150m/s)

Separate sensor

Immersion depth: 130mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

390.00 *
Product no.: 81535M8F3.2

Airflow monitor with linear analogue output

Power supply 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature: -25...+80°C 

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s (optionally up to 150m/s)

Separate sensor

Immersion depth: 165mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

398.00 *
Product no.: 81535M8F3.3

Airflow monitor with linear analogue output

Power supply 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature: -25...+80°C 

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s (optionally up to 150m/s)

Separate sensor

Immersion depth: 300mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

412.00 *
Product no.: 81530F3

Airflow monitor with linear analogue output

Power supply: 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm), 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature1: -25...+80°C 1

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range²: approx. 0.5-30m/s  (adjustable)

Sensor: integrated

Immersion depth: approx. 50mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP67

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1The Monitor is optionally also available with a stepped sensor with a cable length of 2,5m. Above 80°C the sensor needs to be stepped. Then the applicable range of media temperatures increases to -20°C up to 250°C / 350°C.

²Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s, optional 0.1-30m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

425.00 *
Delivery weight: 320 g
Product no.: 81530F3.2

Airflow monitor with linear analogue output

Power supply: 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm), 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature1: -25...+80°C 1

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range²: approx. 0.5-30m/s  (adjustable)

Sensor: integrated

Immersion depth: approx. 165mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP67

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1The Monitor is optionally also available with a stepped sensor with a cable length of 2,5m. Above 80°C the sensor needs to be stepped. Then the applicable range of media temperatures increases to -20°C up to 250°C / 350°C.

²Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s, optional 0.1-30m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

439.00 *
Delivery weight: 320 g
Product no.: 81530F3.3

Airflow monitor with linear analogue output

Power supply: 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm), 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature1: -25...+80°C 1

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range²: approx. 0.5-30m/s  (adjustable)

Sensor: integrated

Immersion depth: approx. 300mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP67

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1The Monitor is optionally also available with a stepped sensor with a cable length of 2,5m. Above 80°C the sensor needs to be stepped. Then the applicable range of media temperatures increases to -20°C up to 250°C / 350°C.

²Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s, optional 0.1-30m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

451.00 *
Delivery weight: 320 g
Product no.: 81530M8F3.1

Airflow monitor with linear analogue output

Power supply 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature: -25...+80°C 

(optionally up to +350°C)

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s (optionally up to 150m/s)

Sensor: integrated

Immersion depth: 130mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

 

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

² Other lengths possible (130/165/250/300mm).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

511.00 *
Product no.: 81530M8F3.2

Airflow monitor with linear analogue output

Power supply 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature: -25...+80°C 

(optionally up to +350°C)

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s (optionally up to 150m/s)

Sensor: integrated

Immersion depth: 165mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

 

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

² Other lengths possible (130/165/250/300mm).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

518.00 *
Product no.: 81530M8F3.3

Airflow monitor with linear analogue output

Power supply 24V DC

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/ not conducting at flow

Media temperature: -25...+80°C 

(optionally up to +350°C)

Temperature gradient: 30K/min

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s (optionally up to 150m/s)

Sensor: integrated

Immersion depth: 300mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

 

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

² Other lengths possible (130/165/250/300mm).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

529.00 *
Product no.: 81530M8F8.1

Airflow monitor with linear analogue output

Power supply 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+250°C 

(optionally up to +350°C)

Temperature gradient: 30K/min 

Switch-point: adjustable via potentiometer

Measurement range1: 0.5-30m/s

(optionally up to 150m/s)

Sensor: integrated

Immersion depth: 130mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

585.00 *
Product no.: 81530M8F8.2

Airflow monitor with linear analogue output

Power supply 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+250°C 

(optionally up to +350°C)

Temperature gradient: 30K/min 

Switch-point: adjustable via potentiometer

Measurement range1: 0.5-30m/s

(optionally up to 150m/s)

Sensor: integrated

Immersion depth: 165mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

593.00 *
Product no.: 81530M8F8.3

Airflow monitor with linear analogue output

Power supply 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+250°C 

(optionally up to +350°C)

Temperature gradient: 30K/min 

Switch-point: adjustable via potentiometer

Measurement range1: 0.5-30m/s

(optionally up to 150m/s)

Sensor: integrated

Immersion depth: 300mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

611.00 *
Product no.: 81530M8F8.1/350°C

Airflow monitor with linear analogue output

Power supply: 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+350°C 

Temperature gradient: 30K/min 

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s

(optionally up to 150m/s)

Sensor: integrated

Immersion depth: 130mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

662.00 *
Product no.: 81530M8F8.2/350°C

Airflow monitor with linear analogue output

Power supply: 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+350°C 

Temperature gradient: 30K/min 

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s

(optionally up to 150m/s)

Sensor: integrated

Immersion depth: 165mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

671.00 *
Product no.: 81530M8F8.3/350°C

Airflow monitor with linear analogue output

Power supply: 24V DC 

Power consumption: 4VA

Signal output flow: 0...10V (Ra=10kOhm, 4...20mA (Ra=0.2kOhm)

Accuracy of signal output: +/-5% of measurement range 

Relay ouput voltage (200VDC/1A): NOC

Behavior at flow: Relay opens 

Transistor ouput: open collector/not conducting at flow

Media temperature: -25...+350°C 

Temperature gradient: 30K/min 

Switch-point: adjustable via potentiometer

Measurement range 1: 0.5-30m/s

(optionally up to 150m/s)

Sensor: integrated

Immersion depth: 300mm

Process connection: PG7

Sensor material: MS58, nickel-plated

Pressure resistance: 10bar

Protection class sensor: IP65

Protection class cabinet: IP54

Cabinet dimension (LxWxH): 56mmx84mmx82mm

1 Other measurement ranges are possible, please send us a note with your order (Default: 0.1-10m/s).

The sensor design may vary.

WEEE-Reg.-Nr. DE 38909112

 

694.00 *
* Prices before VAT, plus delivery